Generators
50 Hz Deutz / Leroy Somer
| Model | Standby power | Prime power | Engine | Alternator | Spec sheet | ||||
|---|---|---|---|---|---|---|---|---|---|
| kVA | kW | kVA | kW | Make | Model | Make | Model | ||
| M-F35 | 35 | 28 | 30 | 24 | DEUTZ | F4L912 | Leroy Somer | LSA42.2L9 | |
| M-F55 | 55 | 44 | 48 | 38 | DEUTZ | F4L912T | Leroy Somer | LSA43.2S35 | |
Standard equipment (Deutz)
- Brand new Joint Venture DEUTZ engine.
- Brand new Leroy Somer AC alternator. Ratings: 230/400 V, 3 Ph, 50 Hz, 1500 rpm, 0.8 PF, IP23, H insulation class.
- Standard radiator mounted on skid.
- AC/DC control panel consisting of: emergency stop button, voltmeter and selector switch, ammeter and selector switch, frequency meter, oil pressure gauge, water temperature gauge, controller DKG507 with following (and not restricted to) features: remote control, AMF, function record, start/stop button, hour run display, high engine temperature shutdown protection, low oil pressure shutdown protection, over speed shutdown protection, alarm output for abnormal operation.
- Circuit breaker & battery charger.
- Anti-vibration elements between engine/alternator and base frame.
- 24 V lead acid battery and battery leads.
- Silencers with flanged flexible connection.
- Open type gensets below 200 kW and all silent type gensets come with a base fuel tank for at least 8 hours running, with fuel gauge integrated in the base frame.
- English operation/maintenance manuals/test report for engine, alternator and genset.
- Standard tools kit.
50 Hz Cummins / Leroy Somer
| Model | Standby power | Prime power | Engine | Alternator | Spec sheet | ||||
|---|---|---|---|---|---|---|---|---|---|
| kVA | kW | kVA | kW | Make | Model | Make | Model | ||
| M-C30 | 30 | 24 | 27.5 | 22 | Cummins | 4B3.9G2 | Leroy Somer | LSA42.2M7 | |
| M-C50 | 50 | 40 | 45 | 36 | Cummins | 4BTA3.9G2 | Leroy Somer | LSA43.2S25 | |
| M-C70 | 70 | 56 | 63 | 50 | Cummins | 4BT3.9-G2 | Leroy Somer | LSA43.2L65 | – |
| M-C100 | 100 | 80 | 90 | 72 | Cummins | 6BT5.9G1 | Leroy Somer | LSA44.2VS3 | |
| M-C110 | 110 | 88 | 100 | 80 | Cummins | 6BT5.9-G2 | Leroy Somer | LSA44.2VS45 | – |
| M-C138 | 138 | 110 | 125 | 100 | Cummins | 6BTAA.9G2 | Leroy Somer | LSA44.2S7 | |
| M-C163 | 163 | 130 | 150 | 120 | Cummins | 6CTA8.3G2 | Leroy Somer | LSA44.2M95 | – |
| M-C206 | 206 | 165 | 188 | 150 | Cummins | 6CTA8.3G2 | Leroy Somer | LSA46.2M3 | |
| M-C215 | 215 | 172 | 200 | 160 | Cummins | 6CTAA8.3G2 | Leroy Somer | LSA46.2M5 | – |
| M-C275 | 275 | 220 | 250 | 200 | Cummins | 6LTAA8.9G2 | Leroy Somer | LSA46.2L6 | |
| M-C313 | 313 | 250 | 275 | 220 | Cummins | NTA855G1A | Leroy Somer | LSA46.2L9 | – |
| M-C350 | 350 | 280 | 313 | 250 | Cummins | NTA855G1B | Leroy Somer | LSA46.2VL12 | |
| M-C388 | 388 | 310 | 350 | 280 | Cummins | NTA855G2A | Leroy Somer | LSA47.2VS2 | – |
| M-C413 | 413 | 330 | 375 | 300 | Cummins | NTAA855G7 | Leroy Somer | LSA47.2VS2 | – |
| M-C450 | 450 | 360 | 413 | 330 | Cummins | NTAA855G7A | Leroy Somer | LSA47.2S4 | – |
| M-C500 | 500 | 400 | 450 | 360 | Cummins | KTA19G3 | Leroy Somer | LSA47.2S5 | – |
| M-C550 | 550 | 440 | 500 | 400 | Cummins | KTA19G4 | Leroy Somer | LSA47.2M7 | – |
| M-C600 | 600 | 480 | 550 | 440 | Cummins | KTAA19G5 | Leroy Somer | LSA47.2M8 | – |
| M-C625 | 625 | 500 | 563 | 460 | Cummins | KTAA19G5 | Leroy Somer | LSA47.2L9 | – |
| M-C650 | Contact us for specifications | – | |||||||
| M-C688 | 688 | 550 | 625 | 500 | Cummins | KTAA19G6A | Leroy Somer | LSA49.1S4A | – |
| M-C825 | 825 | 660 | 750 | 600 | Cummins | KTA38-G2 | Leroy Somer | LSA49.1M65 | – |
| M-C900 | 900 | 720 | 800 | 640 | Cummins | KTA38-G2A | Leroy Somer | LSA49.1M75 | – |
| M-C1000 | 1000 | 800 | 900 | 720 | Cummins | KTA38-G2A | Leroy Somer | LSA49.1L10 | – |
| M-C1100 | 1100 | 880 | 1000 | 800 | Cummins | KTA38-G5 | Leroy Somer | LSG55 | – |
All Cummins generators come with
- Brand new Joint Venture Cummins engine.
- Brand new Leroy Somer AC alternator. Ratings: 230/400 V, 3 Ph, 50 Hz, 1500 rpm, 0.8 PF, IP23, H insulation class.
- Standard radiator mounted on skid.
- AC/DC control panel consisting of: emergency stop button, voltmeter and selector switch, ammeter and selector switch, frequency meter, oil pressure gauge, water temperature gauge, controller DSE702 with following (and not restricted to) features: start/stop button, hour run display, high engine temperature shutdown protection, low oil pressure shutdown protection, over speed shutdown protection, alarm output for abnormal operation.
- Circuit breaker & battery charger.
- Anti-vibration elements between engine/alternator and base frame.
- 24 V lead acid battery and battery leads.
- Silencers with flanged flexible connection.
- Open type gensets below 200 kW and all silent type gensets come with a base fuel tank for at least 8 hours running, with fuel gauge integrated in the base frame.
- English operation/maintenance manuals/test report for engine, alternator and genset.
- Standard tools kit.
Note: gensets below 200 kW/250 kVA come with a base fuel tank for 8 hours operation. Gensets larger than 200 kW/250 kVA have an optional base fuel tank available.
Sound Proof Enclosure
- Robust / highly corrosion resistant construction
- Excellent access for maintenance
- Security and safety
- Transportability
Generator quotes
Call +1 801-225-1180 · fax +1-801-221-2587 · richard.hill@inter-con.us